Foshan shunde top and automatic doors control co., LTD. Automatic door daily operation and inspection
In order to ensure the security of automatic doors, reliable operation, the user or automatic doors in daily management needs of the operation of the automatic door to check.
Test need to be done in the absence of other personnel interference
1, staff from the door or gate at normal speed to the automatic door, automatic door should open automatically, automatic door action should be smooth and no collision occurs; Automatic doors opened, people at a speed of about 150 mm - 150 mm per second slowly through the automatic door, automatic door should remain open;
2, when people leave after induction area, automatic door sensors in delay 1-10 seconds (the length can be set by automatic door switch parameters), automatic door will automatically shut down, the action of automatic doors should be smooth and no collision occurs;
3, observers normal through the automatic door walking routes, need to adjust daily walking routes for personnel is opposite to the automatic door, rather than at a certain Angle to the automatic door;
4, to the automatic door, automatic door sensors induction width should be greater than the width of the door fully open.
5, if the automatic door installation auxiliary light sensors (infrared correlation protection device), when the door is open, people stood still, with the hand keep out auxiliary light sensors, door should remain open. When hand left after a few seconds, the door should be closed.
Note: automatic door fails, please immediately cut off the power automatic doors, and then contact dealers automatic door handle.